Substation Scout

Kewanee

Named in 2 PJM planning documents for 4 projects, from October 18, 2024 to November 15, 2024.

Existingdescribed as
COMEDzone
138 kVkV as printed
4mentions

Also printed as: Kewanee substation

PJM interconnection queue

A PJM queue substation page has the same name: Kewanee (IL) — 6 queue requests filed, 2 active.

Same name and state (weaker). Matched on name and state: the utility that presented this substation operates in one state, and every queue filing at a substation of the same name is in that state. No transmission owner is recorded on those filings, so this is a weaker match than one on owner. Not verified as the same facility.

Projects naming this substation

Figures are from the most recent document naming each project, as printed. Each links to its page.

ProjectStatus as printedCost estimateIn-service dateCustomer loadAs of
ComEd Transmission Zone: Baseline Kewanee Bus 1
b3900.1
Not printed $0.204 M 4/15/2029 Not printed 2024-11-15
SRRTEP Western
ComEd Transmission Zone: Baseline Kewanee 138kV L7411 (74 7411) CB Replacement
b3903.1
Not printed $1.101 M 6/1/2026 Not printed 2024-11-15
SRRTEP Western
ComEd Transmission Zone: Baseline Kewanee 138kV L7411 (74 7411) CB Replacement Not printed $1.101 M 6/1/2026 Not printed 2024-10-18
SRRTEP Western
ComEd Transmission Zone: Baseline Kewanee Bus 1 Not printed $0.204 M 4/15/2029 Not printed 2024-10-18
SRRTEP Western

Every mention

DateDocumentProjectWhat the document says about it
2024-11-15 SRRTEP Western
Item 01 - SRRTEP West - Reliability Analysis Update p. 57
ComEd Transmission Zone: Baseline Kewanee 138kV L7411 (74 7411) CB Replacement “Replace the Kewannee 138 kV kV L7411 circuit breaker with a SF6 circuit breaker.”
138 kV
2024-11-15 SRRTEP Western
Item 01 - SRRTEP West - Reliability Analysis Update p. 60
ComEd Transmission Zone: Baseline Kewanee Bus 1 “Replace the 300 copper conductor with 1113 kcmil ACSR conductor on Kewanee bus No. 1.”
138 kV
2024-10-18 SRRTEP Western
Item 01 - SRRTEP West - Reliability Analysis Update p. 51
ComEd Transmission Zone: Baseline Kewanee 138kV L7411 (74 7411) CB Replacement “Replace the Kewannee 138 kV kV L7411 circuit breaker”
138 kV
2024-10-18 SRRTEP Western
Item 01 - SRRTEP West - Reliability Analysis Update p. 55
ComEd Transmission Zone: Baseline Kewanee Bus 1 “Replace the 300 copper conductor with 1113 kcmil ACSR conductor on Kewanee bus No. 1.”
138 kV

* A local-plan posting carries no meeting date; the date shown is when pjm.com last modified the file.